Cable Type and Installation DetailsMaximum Tensile Load During InstalltionMinimum Bend Radii While Subject to Maximum Tensile Load (During Installation)No Tensile Load (After Installation)
Inside Plant Cable with 2 or 4 Fibers Installed in Cabling Subsystem 1220 N2 Inches1 Inch
Inside Plant Cable with more than 4 FibersPer Manufacturer
Indoor/Outdoor Cable with up to 12 Fibers1335 N20 times of the Outside Diameter (O.D.)10 times of the Outside Diameter (O.D.)
Indoor/Outdoor Cable with more than 12 Fibers2670 N