What is the recommended cable capacity for vertical channels?

Last modified: November 10, 2021
You are here:

The chart below shows the cable fill capacity for ICC vertical cable management channels. The estimates are relatively accurate. The diameter of the cable and the NFPA standard are taken into account. The NFPA79-2012 standard specifies the capacity should not exceed 50%.

Vertical Cable Channels (60% Fill)

Part No.Channel
Size
Width
(in)
Depth
(in)
Usable Area
(In2)
CAT5e
(.1800)
CAT6
(.2120)
CAT6A
(.3400)
Fiber
(.0800)
ICCMSC30BK5"3.754.8918.1817514148230
ICCMSC40BK6"5.665.6328.4126721775358
ICCMSCMA215"3.754.8918.1817514148230
ICCMSCMA225"3.75 (2X)4.89 (2X)18.18 (2X)175 (2X)141 (2X)48 (2X)230 (2X)
ICCMSCMA235"3.75 (2X)4.89 (2X)18.18 (2X)175 (2X)141 (2X)48 (2X)230 (2X)
ICCMSCMA736"5.71527.0826021071342
ICCMSCMA815"3.754.8918.1817514148230
ICCMSCMA825"3.75 (2X)4.89 (2X)18.18 (2X)175 (2X)141 (2X)48 (2X)230 (2X)
ICCMSCMA835"3.75 (2X)4.89 (2X)18.18 (2X)175 (2X)141 (2X)48 (2X)230 (2X)
ICCMSCMA845"3.754.8918.1817514148230